Model name | VDKS-09CB2B | VDKS-12CB2B | VDKS-18CB2B | ||
Power supply | V / Ph / H | 220V / 50Hz | |||
Heating 1 A 7/6ºC W 30/35ºC |
Capacity | kW | 9.20 | 12.10 | 18.70 |
Rated input | kW | 1.99 | 2.50 | 4.02 | |
COP | 4.61 | 4.84 | 4.67 | ||
Heating 2 A 7/6ºC W 40/45ºC |
Capacity | kW | 8.85 | 11.63 | 17.98 |
Rated input | kW | 2.23 | 2.79 | 4.47 | |
COP | 3.97 | 4.17 | 4.03 | ||
Heating 3 A 7/6ºC W 50/55ºC |
Capacity | kW | 8.00 | 10.52 | 16.26 |
Rated input | kW | 2.62 | 3.28 | 5.26 | |
COP | 3.05 | 3.21 | 3.09 | ||
Heating 4 A -7/-8ºC W 30/35ºC |
Capacity | kW | 7.13 | 10.23 | 14.50 |
Rated input | kW | 2.24 | 3.06 | 4.50 | |
COP | 3.18 | 3.34 | 3.22 | ||
Heating 5 A -7/-8ºC W 50/55ºC |
Capacity | kW | 6.20 | 8.16 | 12.61 |
Rated input | kW | 2.95 | 3.69 | 5.91 | |
COP | 2.11 | 2.21 | 2.13 | ||
Heating 6 A -12/-14ºC W 36/41ºC |
Capacity | kW | 6.22 | 8.18 | 12.64 |
Rated input | kW | 2.43 | 3.04 | 4.87 | |
COP | 2.56 | 2.69 | 2.59 | ||
Heating 7 A -20/-ºC W -/41ºC |
Capacity | kW | 5.48 | 7.20 | 11.13 |
Rated input | kW | 2.51 | 3.14 | 5.03 | |
COP | 2.18 | 2.29 | 2.21 | ||
Cooling 8 A35/24ºC W 12/7ºC |
Capacity | kW | 7.90 | 10.40 | 11.40 |
Rated input | kW | 2.62 | 3.42 | 3.87 | |
EER | 3.01 | 3.04 | 2.94 | ||
Seasonal space heating energy efficiency class |
LWT at 35ºC | A+++ | A+++ | A+++ | |
LWT at 55ºC | A++ | A++ | A++ | ||
SCOP | LWT at 35ºC | 4.68 | 4.75 | 4.50 | |
LWT at 55ºC | 4.06 | 4.12 | 3.90 | ||
SEER | LWT at 7ºC | 4.65 | 4.72 | 4.47 | |
Water pressure drop | kPa | 55 | 50 | 50 | |
Refrigerant | Type | R32 | R32 | R32 | |
Charged | kg | 1.5 | 1.8 | 2.1 | |
Compressor | Type | DC inverter | DC inverter | DC inverter | |
Quantity | 1 | 1 | 1 | ||
Capacity | kW | 8.65 | 16.66 | 16.66 | |
Input | kW | 2.26 | 4.30 | 4.30 | |
Fan motor | Fan type | Axial Fan | Axial Fan | Axial Fan | |
Motor type | Brushless DC motor | Brushless DC motor | Brushless DC motor | ||
Motor Quantity | 1 | 2 | 2 | ||
Speed | rpm | 300~1000 | |||
Electronic expansion valve | |||||
Water side heat-exchanger | High efficiency tank | ||||
Sound power level6 | dB | 45 | 46 | 58 | |
Water resistance | IPX4 | IPX4 | IPX4 | ||
Net/Gross weight | Net | kg | 68 | 98 | 108 |
Dimension (L×H×D) | Net | mm | 960*380*820mm | 960*380*1270mm | 960*380*1270mm |
Packing | mm | 1040*505*970mm | 1040*505*1420mm | 1040*505*1420mm | |
Loading quantity (20GP/40GP) | sets | 44/88 | 22/46 | 22/46 | |
Operating temperature | Cooling | ºC | - 5 to 43 | ||
Heating | ºC | - 30 to 35 | |||
DHW | ºC | -30 to 43 |
Molisi Technology was founded in 2004, focusing on heat pump R&D, manufacturing and providing comprehensive energy-saving solutions.
Molisi Technology offers the best solution for heating cooling and hot water supply with dc inverter technology. Vegardis heat pump has always been committed to saving energy. DC inverter EVI technology can effectively reduce power consumption and improve the heating performance of heat pump units to ensure stable performance even at ambient temperatures as low as -35°C.
Molisi Factory has obtained ISO9001, ISO14001,ISO45001 certificates
Main products:
air to water heat pump with R290/R32 refrigerant
EVI air to water heat pump
air source heat pump
Advantage:
15 years exporting experience
Strong R&D team
Custom made service
CE certificate,ERP A+++
As an international enterprise targeting the global market, Molisi attaches great importance to high-end global market, Till now our products have exported to over 30 countries and region.
Vegardis air source heat pump application project
Molisi Company 45KW Air Source Heat Pump Unit Performance Laboratory
Test data range:
1 Cooling and heating capacity
2 Cooling and heating power consumption
3 Cooling and heating performance coefficient
4 Maximum load condition
5 Low temperature working condition
6 Unit system temperature and pressure
7 Water-side pressure loss
8 Measured electro mechanical parameters: voltage, current, power, power factor
Applicable refrigerant: 410A, R134A, R22, R404A, R407A, R290, R32